BR10-PR Series Solid  Dielectric Polemount RECLOSER

Information

BR10-PR series solid dielectric polemount recloser - Ratings : up to 38kV, 800A - Rated interrupting current : 16kA - Short time withstand current(RMS): 16kA/3sec - Interrupting medium : vacuum - Insulation medium : solid(HCEP) - Permanent magnetic actuator with opening and closing coils - Maximum clearing time within 3 cycles - 3 built-in CTs and 6 built-in voltage sensors - Mechanical endurance : 10,000 cycles - Electrical endurance : 10,000cycles at full load - 116 of the number unit operations - Nema pad or universal clamp available - Manual tripping lever, operations counter - Optional manual closing lever - Optional mount bracket for arrester - No electronic components in enclosure of recloser BR-10RN recloser control - Directional O/C, E/F, NPS, and SEF protection - Auto reclosing up to 4 shots - 44 built-in curves & 4 settings group - Alternate settings group as per load flow direction - Load shedding & automatic loop control - Inrush restraint & cold load pickup scheme - Automatic battery management - 4 Auxiliary DO & DI contacts - Voltage calibration for built-in sensor into recloser and factor management by software - Remaining life span calculation of main contacts as per IEEE standard - Dedicated surge protection device for AC supply - Dedicated operating program with remote access features - External indicator outside enclosure - DNP 3.0 & IEC 60870-5-101/104 - Remote control & monitoring via SMS - Password security